MoE Protection Setting Policy
MoE Protection Setting Policy
REVISED FINAL
for
Prepared for:
Prepared by
Page No.
PURPOSE ............................................................................................................................. 1
1 SCOPE ........................................................................................................................... 1
2 REFERENCES ............................................................................................................... 1
3 PROTECTION SETTINGS.............................................................................................. 1
APPENDIX A ....................................................................................................................... 24
i
PROTECTION SETTING POLICY FOR THE MOE’S TRANSMISSION SYSTEM
PURPOSE
This Document defines the Iraq Ministry of Electricity’s (MoE's) policy for the setting of main
protection, back-up protection and fault recorders on Iraq’s 400kV and 132kV systems.
This setting policy has been produced to meet the MoE’s specific requirements for the setting
of protection relays on the Iraqi system and is in general accordance with international best
practice.
1 SCOPE
This Setting Policy document details the protection settings required for feeders,
transformers, reactors, busbars and switchgear associated with MoE's 400kV, and 132kV
systems. This document also details the setting policy for the fault recording function whether
it is applied as standalone equipment or integrated within other equipment.
2 REFERENCES
This Policy makes reference to, or should be read in conjunction with, the following
documents:
MoE Application Policy for the Protection of the Iraq Transmission System
ENA-TS 48-3 – Issue 1 1977 - Energy Networks Association – Technical Specification 48-3
Instantaneous High-Impedance Differential Protection
3 PROTECTION SETTINGS
MoE’s policy for protection settings is laid out in the attached tables. For easy reference a
listing of the tables is given below. An explanation of the abbreviations employed in this
Policy can be found in Appendix A.
If the settings given for the overcurrent and earth fault protection in this Policy cannot be
obtained, the next higher available setting shall be used.
The MoE – Planning and Studies Office shall be consulted when the settings given in this
Policy cannot be achieved or are considered inappropriate.
In addition to the setting recommendations given in this Policy, cognisance should be taken
of relevant manufacturer's setting recommendations.
1
List of Tables
3.1 Feeders 4
2
3.1 Feeders
400kV feeder circuits are equipped with two Groups of protection - Group A and Group B.
For 400kV overhead line (OHL) circuits, Group A shall comprise a distance main protection
(PUTT), stub bus protection, three pole and single pole auto-reclosure, a communicating
directional earth fault protection (POTT), a non-directional 3 phase overcurrent back-up
protection, circuit breaker failure protection and an overvoltage protection. Group B shall
comprise a distance main protection (Blocking), stub bus protection, three pole and single
pole auto-reclosure and non-directional 3 phase overcurrent and earth fault back-up
protection.
For 400kV underground cable feeder circuits, Group A shall comprise a current differential
(unit) main protection with an integral distance protection function and non-directional 3
phase overcurrent and earth fault back-up protection. Group B shall also comprise a current
differential (unit) main protection with an integral distance protection function and non-
directional 3 phase overcurrent and earth fault back-up protection.
132kV feeder circuits are equipped with a single main protection and back-up protection.
For 132kV overhead line circuits the main protection shall be a distance protection (PUTT)
and the back-up protection shall be non-directional 3 phase overcurrent and earth fault.
The protection for 132kV underground feeder circuits and 132kV Overhead Line Feeders of 5
km or less shall comprise a current differential (unit) main protection with an integral distance
protection function and non-directional 3 phase overcurrent and earth fault back-up
protection.
3
Protection Setting
The settings shall be determined in accordance with the relevant
manufacturer's instructions to satisfy the following requirements:-
400kV and 132kV Plain Underground Cable Feeders and 400kV and 132kV
Overhead Line Feeders of 5 km or Less (Note 2)
(i) The minimum credible in zone fault current shall produce a multiple of relay
Unit fault setting of at least 1.5.
(ii) The protection shall operate for all types of faults within the protected zone
with a minimum fault resistance (RF) of 100 . The protection shall be set with
sensitivity consistent with security criteria. (Note 1).
(iii) Special care is required to compensate for the underground cable capacitive
current.
Distance 400kV and 132kV Plain Underground Cable Feeders and 400kV and 132kV
(Note 3 and 4) Overhead Line Feeders of 5 km or Less (Note 2)
Zone 1
(i) Zone 1 disabled (as overhead line circuits are of 5km or less and typically
cable circuits are usually relatively short)
Zone 2
(i) Reach at line angle - 150% of the protected circuit pps impedance.
Zone 2 should not reach through transformers at the remote busbar. If this
cannot be achieved, the Zone 2 reach of the distance protection shall be set to
cover 100% of the protected line and to provide back up protection for as much
of the shortest line out of the remote busbar as is possible without reaching
through the transformer.
Zone 3
Zone 3 should not reach into the lower voltage circuits of transformers at
remote busbars. If this cannot be achieved, the Zone 3 reach of the distance
protection shall be set to cover 100% of the protected line and to provide
backup protection for as much of the longest line out of the remote busbar as is
possible without risk of non-discrimination with transformer lower voltage
protection.
4
(ii) Time delay – 0.8 s.
Distance
(Note 3 and 4) 400kV (Group A) Distance Protection and 132kV Distance Protection on
Plain Overhead Line Feeders Greater than 5km
Zone 1
(i) Reach at line angle - 80% of the protected line pps impedance - PUTT
(ii) Time delay - 0 s.
Zone 2
(i) Single circuit OHL - Reach at line angle - not less than 120% of the
protected circuit pps impedance but not more than 100% of protected line
pps plus 50% of shortest line pps out of remote busbar.
Double Circuit OHLs - To cater for the effects of zero sequence mutual
coupling, ideally a setting of 150% of the protected line pps impedance
should be selected, provided that this does not exceed 100% of protected
line pps impedance plus 50% of shortest line pps impedance out of the
remote busbar. Where this cannot be achieved, advice should be sought
from the MoE Planning and Studies office. Consideration could then be
given to co-ordinating the Zone 2 time delays or of applying a reverse Zone
4 reach with a Zone 2 time delay at the remote end.
In addition to the above, Zone 2 should not reach through transformers at the
remote busbar. If this cannot be achieved, the Zone 2 reach of the distance
protection shall be set to cover 100% of the protected line and to provide back
up protection for as much of the shortest line out of the remote busbar as is
possible without reaching through the transformer.
Zone 3
(i) Zone 3 forward reach at line angle = larger of 160% of protected circuit
pps impedance or (protected circuit pps impedance + 120% of longest
remote outgoing feeder pps impedance)
Zone 3 should not reach into the lower voltage circuits of transformers at
remote busbars. If this cannot be achieved, the Zone 3 reach of the distance
protection shall be set to cover 100% of the protected line and to provide
backup protection for as much of the longest line out of the remote busbar as is
possible without risk of non-discrimination with transformer lower voltage
protection.
5
Distance
(Note 3 and 4) 400kV (Group B) Distance Protection on Plain Overhead Line Feeders
Greater than 5km
Zone 1, Zone 2 and Zone 3 settings are the same as for Group A distance
protection
(i) Reverse reach must be greater than the over-reach of the Zone 2 distance
relay at the remote end including a margin to cater for measurement
errors, CT/VT tolerances and inaccuracies in the circuit impedances.
6
Distance 132kV Three-ended Overhead Line Feeders with a Teed transformer (e.g.
(Note 3 and 4) Teed mobile substation with associated 132kV Circuit Breaker)
Zone 1
(i) Reach at line angle - 80% of the protected line pps impedance
to the electrically nearer of the remote substations (i.e. the
remote end substation and the Teed transformer) – PUTT (2
ended )
(ii) Time delay - 0 s.
Zone 2
(i) Reach at line angle – 150% of the protected circuit pps (to the
furthest remote end).
(ii) Time delay – 0.4s
Zone 3
General
Distance Residual Compensation
Protection
Settings Residual compensation factor shall be set in accordance with the relevant relay
manufacturer’s instructions (Note 5).
7
General Quadrilateral Resistive Reach Settings
Distance
Protection Distance protection resistive reach settings of the quadrilateral characteristics
Settings should accommodate the circuit resistance, fault arc resistance and tower
footing resistance (in the case of earth faults) whilst maintaining an adequate
margin with load impedance.
Minimum load impedance can be determined from the following formula:
Z load min = (Vmin/ 3)/Imax
Where: Vmin = minimum phase to phase voltage (say 0.9 x V nominal)
Imax = maximum load current
R load min = cos x Z load min
Where: = maximum load impedance angle (cos = power factor) related to
minimum load conditions
Typically the phase resistive reach should a have a margin of 40% and the earth
resistive reach a margin of 20% with the load minimum resistance.
In addition, relay manufacturers often recommend a limit to the magnitude of
the resistive reach settings in order to achieve specified relay accuracy and
performance, these limits shall not be exceeded.
Switch-on-to-fault
(ii) Recognition of line energization – automatic pole dead logic (i.e. Using
voltage and current level detectors)
Distance Schemes
A Permissive Under Reach Transfer Trip scheme (PUTT) shall be applied for
the Group A distance protection on 400kV overhead line circuits and for the
distance protection on 132kV overhead line circuits.
8
General Underground cable circuits which employ a unit protection incorporating a
Distance distance protection function shall operate as a non-communicating plain
Protection distance protection.
Settings
Setting Groups
To cater for the effects of zero sequence mutual coupling, two setting groups
shall be applied for overhead line circuits which are run in parallel for the
majority of their length
Settings as above for Group A and Group B 400kV and 132kV Plain
Overhead Line Feeders
(ii) Group 2 – for the case when one of the parallel circuits is in service, but
the other parallel circuit is isolated and earthed at both ends. For this
situation the active setting group of the distance protection on the in-
service circuit should be switched manually or through SCADA from
Setting Group 1 to Setting Group 2 which should be set as follows:
Zone 1:
To cater for the tendency of Zone 1 overreaching for faults beyond the
line end, the following reduced reach settings should be applied:
Fault Locator
Fault locator shall be activated. See section 3.9 for further information.
Back-up 400kV and 132kV Overhead Line and Underground Cable Circuits
Overcurrent
Back-up 3 phase non-directional overcurrent protection is applied to MoE 400kV
and 132kV feeder circuits.
The current setting above should also be no more than 75% of the minimum
phase to phase fault current infeed for a remote end fault. If this condition is not
satisfied advice should be sought from the MoE Planning and Studies office.
Back-up 400kV and 132kV Overhead Line and Underground Cable Circuits
Earth fault
Back-up non-directional earth fault protection is applied to MoE 400kV and
132kV feeder circuits.
The earth fault protection shall be set to 20% CT nominal current with a
standard inverse characteristic and a time multiplier setting which will allow a
clearance time of around 1 sec for a remote end earth-fault with maximum fault
infeed at the local end.
The earth fault current setting above should also be no more than 40% on the
minimum earth fault current infeed for a remote end fault. If this condition is not
satisfied advice should be sought from the MoE Planning and Studies office.
The directional earth fault protection shall operate in conjunction with a tele-
protection channel to form a directional comparison permissive overreach
scheme with echo feature. The communication aided directional earth fault
protection shall be set to 10% CT nominal current with a 200ms time delay in
order to provide co-ordination with the distance protection function. The Relay
Characteristic angle shall be set in accordance with the relay manufacturer’s
recommendations (depending on the type of DEF relay, the relay characteristic
angle may be negative or positive).
Notes:
1 With load biased types of protection, 100 sensitivity may not be achievable during short duration
overloads; however for load current conditions of less than 1.5 times the relay nominal current, a
sensitivity of at least 100 shall be achieved.
2 All underground cable circuits and overhead line circuits of 5 km or less are to be equipped with
current differential unit protection.
For 400kV underground circuits and 400kV overhead line circuits of 5 km or less, a unit
protection relay with an integral distance protection function shall be provided for each of the
two groups of protection (i.e. Group A and Group B).
For 132kV underground circuits and 132kV overhead line circuits of 5 km or less, a single unit
protection relay with an integral distance protection function shall be provided.
The integral distance protection function in the 400kV Group A and the single 132kV unit protection
relays shall be enabled. The distance protection function shall operate as a plain distance
protection (non-communicating) scheme.
10
3 The Zone 2 and Zone 3 reach settings shall be consistent with loading requirements given in Note
4. Quadrilateral characteristics, where available, shall be used in preference to the shaped or
circular ones. The use of load blinders may be necessary to prevent load encroachment, in which
case the settings shall be determined in accordance with the relevant manufacturer's instructions.
In exceptional circumstances, where load encroachment cannot be avoided, consideration will be
given to reducing maximum line loading.
5 Special care must be taken in setting the residual compensation factor for cable circuits due to the
following: (i) The angle of the zero sequence impedance of cable circuits could be significantly
different from that of the positive sequence impedance, and/or (ii) The required residual
compensation factor could be negative.
11
3.1.1 Auto-reclose
Protection Setting
Auto On 400kV over head line circuits at one and a half circuit breaker configuration
Reclose substations, sequential reclosing of the busbar circuit breaker and tie (middle)
circuit breaker is recommended.
For 400kV over head line circuits where single pole circuits breakers are available,
single pole high speed auto reclosing is applied with the following settings:-
1
Dead time of busbar circuit breaker = 0.8 seconds
2
Dead time of tie (middle) circuit breaker = 1.2 seconds
3
Reclaim time = 30 seconds.
Note 1: These are typical settings, however, in some circumstances e.g. long lines,
may require a longer dead time to ensure that the secondary arc is
extinguished. If necessary power system studies should be performed to
establish the deionisation time for these circumstances.
Note 2: If the busbar circuit breaker fails to reclose, reclosing of the tie
(middle) circuit breaker should be blocked.
Note 3: The reclaim time should be compatible with the circuit breaker open-close
duty cycle.
For 132kV over head line circuits, three pole gang operated circuits breakers are
utilized and three pole high speed auto reclose is applied with the following
settings:-
12
3.1.2 Broken Conductor Protection
Protection Setting
Broken The following settings shall be applied for 400kV and 132kV overhead line circuits:-
Conductor
protection Where the broken conductor protection detection is based on measuring
the ratio of the standing negative phase sequence current to standing
positive phase sequence current the following settings should be applied:
I2/I1 = 200%
13
3.2 400kV and 132kV Busbars
Protection Setting
Busbar High impedance busbar schemes based on the circulating current differential
principle with high impedance relays:
Low impedance busbar schemes based on the low impedance biased differential
current principle – the settings shall be determined in accordance with the
manufacturer’s recommendations (Note 2).
Overall fault setting – between 10% and 50% of the fault current available for
faults on the busbars under minimum plant conditions (Note 1).
(i) Current - 10% of the full load rating of the busbar (Note 3).
(ii) Time delay - 3 s.
Notes:
1 The fault settings of individual protection zones shall meet the following requirements:
(a) The fault setting of the check zone and the minimum fault setting of the individual
discriminating zones shall be equal to approximately 50% of the full load rating of the
associated busbar.
(b) The maximum fault setting of the individual discriminating zones shall not exceed the full load
rating of the associated busbar.
(c) When two or more sections of busbar are connected together via section disconnectors and
the combined discriminating zone gives rise to a fault setting in excess of the full load current
rating of the associated busbar, the minimum fault setting of the individual discriminating
zones shall be reduced below 50% to achieve a combined fault setting equal to or less than
the full load rating of the associated busbar.
2 The minimum threshold setting shall be set to the lesser of the following:
3 Subject to the setting not exceeding 50% of the anticipated full load current rating of any single
connected circuit. For low impedance protection working on biased differential current, the
differential current alarm shall be set to 10% of busbar rating, and time delay 3s. This is to prevent
a spurious alarm being generated with maximum through load with the worst possible CT error,
bearing in mind that for low impedance busbar protection schemes Class P CTs can be used in
lieu of Class X CTs.
14
3.3 Bus Sections and Bus Couplers
Protection Setting
400kV and 132kV
OC (IDMT)
Overcurrent Current Setting = As near as possible to busbar continuous current rating
Time multiplier setting = to ensure that under maximum fault condition, operation
is not faster than 1 sec.
EF (IDMT)
Earth fault 400kV and 132kV
Time multiplier setting = to ensure that under maximum fault condition, operation
is not faster than 1 sec.
15
3.4 Transformers
Protection Setting
Overall
Differential (low
impedance Current – 10% - 60% rated ITX HV WINDING - preferred setting 15%.
biased
differential)
High Impedance
Circulating Settings in accordance with ENA-TS 48-3
Current
Differential
Notes:-
1 As per IEC 60076-5, the transformer must withstand 2 seconds under maximum let through fault
conditions.
.
3.4.2 132/33kV and 132/11kV Double -Wound-Transformers
Protection Setting
Overall
Differential
(low Current - 10% - 60% transformer HV winding rating - preferred setting 15%.
impedance
biased
differential)
132kV
restricted Low Impedance settings as per manufacturer recommendations
Earth Fault
Protection High Impedance settings in accordance with ENA-TS 48-3
17
Protection Setting
Notes:-
1 As per IEC 60076-5, the transformer must withstand 2 seconds under maximum let through fault
condition.
2 As the transformer neutral carries earth fault current for any earth fault on the 132kV system, the
maximum transformer neutral current must be calculated for an external earth fault and a current
setting above this value must be selected. This will ensure that the transformer SBEF will not trip
for a feeder earth fault.
Protection Setting
Overall
Differential
(low impedance Current - 10% - 60% transformer HV winding rating - preferred setting 15%.
biased
differential)
132kV restricted
Earth Fault Low Impedance settings as per manufacturer recommendations
Protection
High Impedance settings in accordance with ENA-TS 48-3
18
Protection Setting
Notes:-
1 As per IEC 60076-5, the transformer must withstand 2 seconds under maximum let through fault
condition.
19
3.5 Reactors
Protection Setting
High Impedance
Circulating
Current Current - 10% - 25% reactor rated current - preferred setting 15% (Note 3)
Overall
Differential
Current – 400% reactor rated current
Time – Instantaneous
High Set
Overcurrent
Oil and Winding Oil Temp - Alarm - 90 C or in accordance with the manufacturer’s
Temperature recommendations.
(Note 1) Oil Temp – Trip - 100 C or in accordance with the manufacturer’s
recommendations.
Notes:-
1 To comply with manufacturer’s recommendations, a tolerance of 5 C is acceptable.
3 Guidance on the setting of high impedance circulating current differential protection schemes
is given in ENA-TS 48-3
20
3.6 Circuit Breaker Fail Protection
Protection Setting
Current Check Setting
Circuit
Breaker 10% of CT rated secondary current
Fail .
In the event of a circuit breaker failing to open within a pre-selected time, the breaker
failure protection (CBF) shall after a 140 ms time delay initiate tripping of all circuit
breakers connected to the same bus bar as the failed circuit breaker and if necessary
shall simultaneously initiate an intertrip of the remote circuit breaker/s associated with
the failed circuit breaker.
Check synchronising is used when switching two parts of a system which are weakly tied together
via other paths elsewhere in the system. In this synchronous system there should be no frequency
difference across the breaker but there may be significant differences in phase angle and voltage
magnitude due to differences in circuit lengths and loadings.
System synchronising is used when switching an islanded system in order to re-parallel it to the rest
of the transmission system. In this asynchronous system there may be a frequency difference
across the circuit breaker in addition to phase angle and voltage magnitude differences.
Standard settings for check and system synchronising functions are given below. For the majority
of cases these setting should be adequate, but unusual system configurations or operating
conditions may require that these setting be reviewed.
Protection Setting
The following settings shall be applied for 400kV:-
Check and The phase angle difference setting for check synchronising =
System 35°
Synchronising
The phase angle difference setting for system synchronising =
10°
21
The following settings shall be applied for 132kV:-
The phase angle difference setting for check synchronising =
20°
Protection Setting
Stage 1 Alarm Voltage setting = 1.15 x Vn
400kV OHL Time Delay = 20 secs
Overvoltage
Protection Stage 2 Trip Voltage setting = 1.20 x Vn
Time Delay = 3 secs
Protection Settings
(iv) Frequency: f< = 49.5 Hz, f> = 50.5 Hz, Frequency gradient: ± 0.4 Hz/s.
To avoid triggering in case the feeder is manually switched off, frequency to be
triggered at busbars only.
22
Recording Duration:
Clock:
Channel Labeling
The analogue and event channels shall be labeled with their appropriate name.
e.g. Red phase current – IR, Group A Main Protection Trip Relay - FMP TR.
Notes:-
1 If nuisance triggering is experienced then the triggering levels should be adjusted accordingly
for affected circuits.
3 Where the fault recording function is integrated within a protection relay, this setting may be
fixed by the protection equipment and so may not be able to be set differently for fault
recording.
4 The required distance to fault setting information (line impedance per km and line length)
should be recorded with the equipment’s other setting information as part of the settings
schedule.
5 Where more than one equipment type on a feeder bay, has a fault location facility, (e.g.
distance relay and bay controller with integrated fault recorder), then all equipment shall be
set and enabled to provide confirmatory evidence of a fault location.
6 The fault locator need not be set for circuits of short route length Typically, these will be
circuits that are so short that a distance relay could not be deployed e.g. the distance relay
does not have the settings capability for such a short distance (say < 5km) or no 3 phase VTs
exist on a cable circuit.
7 For current Differential schemes, fault location with measurements from both ends of the
line should be activated.
23
Appendix A - List of Abbreviations
APPENDIX A
LIST OF ABBREVIATIONS
Z1 - positive sequence impedance of one circuit of a double-circuit line in which the other
circuit is open circuited at each end.
Z0 - zero sequence impedance of one circuit of a double-circuit line in which the other
circuit is open circuited at each end.
RF - fault resistance.
SI – Standard Inverse 30 times Definite Time Curve (overcurrent or earth fault protection)
- three phase.
VT – Voltage Transformer
CT – Current Transformer